Isolated Footing Design

Geotechnical IS 456:2000~3 min

Design an isolated RCC footing for a column load as per IS 456:2000.

Formula

A_req = P / SBC; Mu = qu × (L-a)² / 8

Input Parameters

Results

Required Footing Area
4.40m²
Footing Size (L = B)
2.10m
Net Upward Pressure (qu)
204.55kN/m²
Required Depth (d)
219mm

Step-by-Step Method

  1. 1Assume 10% self-weight of footing: Total load = 1.1P.
  2. 2Required area = Total load / SBC.
  3. 3Footing size L = √(Area) for square footing.
  4. 4Net upward pressure qu = Pu / A.
  5. 5Design for bending moment at face of column.

Engineering Notes

  • •Minimum depth of footing = 500 mm below NGL.
  • •Minimum concrete cover = 50 mm for footings.
  • •Check punching shear at d/2 from column face.

Code Reference

IS 456:2000